Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 261
Accessories Chapter 12
Recommended thermostat control wiring to prevent dynamic brake overheating.
Figure 93 - Thermostat Control Wiring
Sensorless Vector Control (SVC) Recommended Dynamic Brake
Modules for Option DB1 (IP67 Resistor)
➊ Drive rating and DB part numbers are not interchangeable. Only use specified resistor. Customer is responsible to evaluate if
performance meets application requirement.
Note: Duty Cycle listed is based on full speed to zero speed deceleration. For
constant regen at full speed, duty cycle capability is half of what is listed.
Application Type 1 represents maximum capability up to 100% braking torque
where possible.
3-Phase
Power
R (L1)
S (L2)
T (L3)
(M)
Contactor
Power On
Power Source DB Resistor Thermostat
Power Off
M
M
Drive and
Motor Size
kW Cat. No. ➊
Resistance
Ohms ± 5%
Continuous
Power kW
Max Energy
kJ
Max Braking
Torque % of
Motor
Application Type 1 Application Type 2
Braking
Torque % of
Motor
Duty
Cycle %
Braking
Torque % of
Motor
Duty
Cycle %
380…480 Volt AC Input Drives
0.37 (0.5)
284R-360P500-M* 360 0.086 17 305% 100% 47% 150% 31%
0.75 (1)
284R-360P500-M* 360 0.086 17 220% 100% 23% 150% 15%
1.5 (2)
284R-360P500-M* 360 0.086 17 110% 100% 12% 110% 11%
2.2 (3)
284R-120P1K2-M* 120 0.26 52 197% 100% 24% 150% 16%
4 (5)
284R-120P1K2-M* 120 0.26 52 124% 100% 13% 124% 10%