Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 197
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
129 Torque Current
Displays the current value of the motor torque current
as measured by the drive.
Read Only Drive Display 284E
131 Motor NP Volts
Set to the motor name plate rated volts.
Based on Drive Rating Drive Setup 284E
132 Motor NP Hertz
Set to the motor nameplate rated frequency.
60 Hz Drive Setup 284E
133 Motor OL Current
Set to the maximum allowable current.
Based on Drive Rating Drive Setup 284E
134 Minimum Freq
Sets the lowest frequency the drive will output
continuously.
0.0 Hz Drive Setup 284E
135 Maximum Freq
Sets the highest frequency the drive will output
continuously.
60 Hz Drive Setup 284E
136 Start Source
Sets the control scheme used to start the Bulletin 284E
ArmorStart.
5 = Comm Port
(RS485 (DSI))
Drive Setup 284E
137 Stop Mode
Sets the Valid Stop Mode for the Bulletin 284E
ArmorStart.
9 =
Ramp + EM Brk
Drive Setup 284E
138 Speed Reference
Sets the Valid Speed References for the Bulletin 284E
ArmorStart.
5 = Comm Port Drive Setup 284E
139 Accel Time 1
Sets the rate of acceleration for all speed increases.
10.0 Secs Drive Setup 284E
140 Decel Time 1
Sets the rate of deceleration for all speed decreases.
10.0 Secs Drive Setup 284E
141 Reset To Defaults
Used to reset drive to factory default settings
0 = Ready/Idle Drive Setup 284E
142 Option not valid for Bulletin 284E ArmorStart.
143 Motor OL Ret
Enables/Disables the Motor Overload Retention
function.
0 = Disabled Drive Setup 284E
Table 28 - ArmorStart Common Parameters
Parameter
Number Parameter Name Description Factory Default Group Controller
Table 29 - Parameter Descriptions
Parameter
Number
Parameter
Name
Description Factory Default Group
151…154
Digital In 1 Sel
Digital In 2 Sel
Digital In 3 Sel
Digital In 4 Sel
Selects the function for the digital inputs.
See Table 20. Drive Advanced Setup
155 Relay Out Sel
Sets the condition that changes the state of the output
relay contacts.
0 = Ready/Fault
See Table 21.
Drive Advanced Setup
156 Relay Out Level
Sets the trip point for the digital output relay if the value of
Parameter 155 (Relay Out Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.
0.0 Drive Advanced Setup
158 Reserved
— —
Drive Advanced Setup
159 Reserved
— —
Drive Advanced Setup
161 Reserved
— —
Drive Advanced Setup
162 Reserved
— —
Drive Advanced Setup
164 Reserved
— —
Drive Advanced Setup
165 Option not valid for Bulletin 284E ArmorStart.
166 Option not valid for Bulletin 284E ArmorStart.