222 Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 9 Diagnostics
c. You should see the yellow inhibit symbol next to the ArmorStart in the
I/O Configuration tree showing that the module is inhibited.
10. Execute the instruction by toggling the Reset input that was created
earlier.
a. Energize the bit by left mouse clicking on the input and pushing
CTRL+T. De-energize the bit with CTRL+T again.
b. You should see the status LEDs on the ArmorStart display the Reset
and Power Cycle sequence. You should also see the Done (DN) bit of
the message turn green indicating that the reset was successful.
11. Verify the reset worked by bringing the ArmorStart's web browser back up
and verifying that the User Name is Administrator and that there is no set
password.
12. Uninhibit the ArmorStart module through the AOP and plug any I/O
connections back into the ArmorStart.