148 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
OutA Pr FltValue
This parameter determines the state
the Output A assumes when a trip
occurs and Parameter 33 (OutA Pr
FltState) is set to “0”.
0 = Open
1 = Close
Parameter Number 34
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Net FltState
This parameter in conjunction with
Parameter 36 (OutA Net FltValue)
defines how Output A will respond
when a network fault occurs.
0 = Goto Net FltValue
1 = Hold Last State
When set to “1”, Output A will hold
state prior to trip occurrence. When set
to “0”, Output A will open or close as
determined by the setting in
Parameter 36.
Parameter Number 35
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Net FltValue
This parameter determines the state
that Output A assumes when a
network fault occurs and Parameter
35 (OutA Net FltState) is set to “0”.
0 = Open
1 = Close
Parameter Number 36
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
OutA Net IdlState
This parameter in conjunction with
Parameter 38 (OutA Net IdlValue)
defines how Output A will respond
when the network is idle.
0 = Goto Net IdlValue
1 = Hold Last State
When set to “0”, Output A will open or
close as determined by the setting in
Parameter 38.
Parameter Number 37
Access Rule GET/SET
Data Type BOOL
Group User I/O Config.
Units —
Minimum Value 0
Maximum Value 1
Default Value 0