178 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
SW Current Trip
Enables/disables a software
instantaneous (within 100 ms)
current trip.
Parameter Number 198
Related Parameters 133
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units 0.1 A
Minimum Value 0.0
Maximum Value Drive rated amps x 2
Default Value 0.0 (Disabled)
Process Factor
Scales the output frequency value
displayed by Parameter 110 (Process
Display).
Output Freq x Process Factor = Process
Display
Parameter Number 199
Related Parameters 110
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units 0.1
Minimum Value 0.1
Maximum Value 999.9
Default Value 30.0
Fault Clear
Stop drive before changing this
parameter.
Resets a fault and clears the fault
queue. Used primarily to clear a fault
over network communications.
0 = Ready/Idle (Default)
1 = Reset Fault
2 = Clear Buffer (Parameters
107…109 (Fault x Code))
Parameter Number 200
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units —
Minimum Value 0
Maximum Value 2
Default Value 0
Program Lock
Protects parameters against change
by unauthorized personnel.
0 = Unlocked
1 = Locked
Parameter Number 201
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units —
Minimum Value 0
Maximum Value 1
Default Value 0