Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 179
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Testpoint Sel
Used by Rockwell Automation field
service personnel.
Parameter Number 202
Related Parameters 119
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units 1 Hex
Minimum Value 0
Maximum Value FFFF
Default Value 400
Comm Data Rate
This parameter is not available for
use with the ArmorStart Distributed
Motor Controller.
Parameter Number 203
CommNode Addr
This parameter is not available for
use with the ArmorStart Distributed
Motor Controller.
Parameter Number 204
Comm Loss Action
Selects the drives response to a loss of
the communication connection or
excessive communication errors.
0 = Fault (Default)
Drive will fault on an F81 Comm Loss
and coast to stop
1 = Coast Stop
Stops drive via coast to stop
2 = Stop
Stops via Parameter 137 (Stop Mode)
setting
3 = Continue Last
Drive continues operating at
communication commanded speed
saved in RAM.
Parameter Number 205
Related Parameters 115, 137, 206
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units
Minimum Value 0
Maximum Value 3
Default Value 0