146 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Str Net FltState
This parameter in conjunction with
Parameter 27 (Str Net FltValue)
defines how the starter will respond
when a fault occurs as determined by
Parameter 27.
0 = Goto Fault Value
1 = Hold Last State
Allows Starter to hold last state or go
to FltValue on NetFaults.
Parameter Number 26
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Str Net FltValue
This parameter determines how the
starter will be commanded in the
event of a fault. State the Starter
will go to on a Net Flt if Parameter
26 (Str Net FltState) = 0 (Goto Fault
Value).
0 = OFF
1 = ON
Parameter Number 27
Access Rule GET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Str Net IdlState
This parameter in conjunction with
Parameter 29 (Str Net IdlValue)
defines how the starter will respond
when a network is idle as determined
by Parameter 29.
0 = Goto Idle Value
1 = Hold Last State
Parameter Number 28
Access Rule GET/SET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0
Str Net IdlValue
This parameter determines the state
that starter assumes when the
network is idle and Parameter 28 (Str
Net IdlState) is set to “0”.
0 = OFF
1 = ON
Parameter Number 29
Access Rule GET
Data Type BOOL
Group Starter Protection
Units —
Minimum Value 0
Maximum Value 1
Default Value 0