Rockwell Automation Publication 280E-UM001B-EN-P – July 2012 131
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Phase B Current
This parameter provides the current of
Phase B measured in increments of
1/10
th
of an ampere.
Parameter Number 102
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
Phase C Current
This parameter provides the current of
Phase C measured in increments of
1/10
th
of an ampere.
Parameter Number 103
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
Average Current
This parameter provides the average
current measured in increments of
1/10
th
of an ampere.
Parameter Number 104
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0
Therm Utilized
This parameter displays the
% Thermal Capacity used.
Parameter Number 105
Access Rule GET/SET
Data Type USINT
Group Starter Display
Units % FLA
Minimum Value 0
Maximum Value 100
Default Value 0