Rockwell-automation 284E ArmorStart with EtherNet/IP - User Manual Manuale Utente Pagina 233

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 348
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 232
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 233
Troubleshooting Chapter 10
Control Module Removal
1. Disconnect power by going to the control module and turning OFF the
At-Motor disconnect and performing lockout-tagout per your company
policy.
2. Remove motor cable.
3. Loosen the four mounting screws.
4. Unplug the Control module from the base by pulling forward.
Installation of Control Module
5. Install control module.
6. Tighten four mounting screws.
7. Install motor cable.
Figure 84 - Control Module Replacement
ATTENTION: To avoid shock hazard, disconnect main power before working on the
controller, motor, or control devices.
2
1
4
3
5
6
7
Motor Cable
30 lb•in./
3.39 N•m
Note: DeviceNet™ base module is shown.
Vedere la pagina 232
1 2 ... 228 229 230 231 232 233 234 235 236 237 238 ... 347 348

Commenti su questo manuale

Nessun commento