196 Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
105 Therm Utilized
This parameter displays the % Thermal Capacity used.
0Starter DisplayDOL
106 FLA Setting
The motor’s full load current rating
See Table 19. Starter Setup DOL
107 Overload Class
Selects the overload class.
1 =
Overload Class 10
Starter Setup DOL
108 OL Reset Level
Selects the % Thermal Capacity which an overload can
be cleared.
75 Starter Setup DOL
101 Output Freq
Output frequency present at T1, T2 & T3 (U, V & W)
Read Only Drive Display 284E
102 Commanded Freq
Value of the active frequency command
Read Only Drive Display 284E
103 Output Current
Output current present at T1, T2 & T3 (U, V & W)
Read Only Drive Display 284E
104 Output Voltage
Output voltage present at T1, T2 & T3 (U, V & W)
Read Only Drive Display 284E
105 DC Bus Voltage
Present DC bus voltage level
Read Only Drive Display 284E
106 Drive Status
Present operating condition of the drive.
Read Only Drive Display 284E
107…109 Fault x Code
A code that represents a drive fault.
Read Only Drive Display 284E
110 Process Display
The output frequency scaled by Parameter 199 (Process
Factor).
Read Only Drive Display 284E
112 Control Source
Displays the source of the Start Command and Speed
Reference.
5 =
RS485 (DSI) Port
Drive Display 284E
113 Option not valid for Bulletin 284E ArmorStart.
114 Dig In Status
Status of the control terminal block digital inputs.
0Drive Display284E
115 Comm Status
Status of the communications ports
0Drive Display284E
116 Control SW Ver
Main Control Board software version for AC Drive.
Read Only Drive Display 284E
117 Drive Type
Used by Rockwell Automation field service personnel.
Read Only Drive Display 284E
118 Elapsed Run Time
Accumulated time drive is outputting power.
Read Only Drive Display 284E
119 Testpoint Data
The present value of the function selected in Parameter
202 (Testpoint Sel).
Read Only Drive Display 284E
120 Option not valid for Bulletin 284E ArmorStart.
121 Option not valid for Bulletin 284E ArmorStart.
122 Output Power
Output power present at T1, T2 & T3 (U, V & W).
Read Only Drive Display 284E
123 Output Power Fctr
The angle in electrical degrees between motor voltage
and motor current.
Read Only Drive Display 284E
124 Drive Temp
Present operating temperature of the drive power
section.
Read Only Drive Display 284E
125 Counter Status
The current value of the counter when counter is
enabled.
Read Only Drive Display 284E
126 Timer Status
The current value of the timer when timer is enabled.
Read Only Drive Display 284E
128 StpLogic Status
When Parameter 138 (Speed Reference) is set to "6"
(StpLogic), this parameter will display the current
StepLogic profile as defined by Parameters 240-247
(StpLogic x).
Read Only Drive Display 284E
Table 28 - ArmorStart Common Parameters