Rockwell Automation Publication 280E-UM001B-EN-P - July 2012 241
Specifications for EtherNet/IP Chapter 11
➊ Add power requirements for outputs (1 A max.) to A1/A2.
➋ Add power requirements for inputs (200 mA max.) to A3/A2.
➌ If A1 power is disconnected.
UL/NEMA IEC
Standards Compliance
UL 508
CSA C22.2, No. 14
EN/IEC 60947-4
EN/IEC 60947-4-1
CE Marked per Low Voltage 2006/95/EC
EMC Directive 2004/108/EC
CCC
ODVA for EtherNet/IP
Certifications cULus (File No. E3125, Guides NLDX, NLDX7)
EtherNet/IP Version – Control and I/O Power Requirements
A1/A2
➊ A3/A2 ➋ A1/A2 ➊ A3/A2 ➋ A3/A2 ➌
Units W/O HOA W/ HOA
Control Voltage Volts 24V DC
Module Inrush Amps 0.92 0.30 1.09 0.125 0.295
Module Steady Amps 0.06 0.30 0.23 0.125 0.295
Total Control Power (Pick Up) Watts 22.08 7.20 26.16 3.00 7.08
Total Control Power (Running) Watts 1.44 7.20 5.52 3.00 7.08
UL/NEMA IEC
Input Ratings – Sourced from
Control Circuit
(A3/A2)
Rated Operation Voltage 24V DC
Input On-State Voltage Range 10…26V DC
Input On-State Current
3.0 mA @ 10V DC
7.2 mA @ 24V DC
Input Off-State Voltage Range 0…5V DC
Input Off-State Current <1.5 mA
Input Filter – Software Selectable
Off to On Settable from 0…64 ms in 1 ms increments
On to Off Settable from 0…64 ms in 1 ms increments
Input Compatibility N/A IEC 1+
Number of Inputs 4
Sensor Source
Voltage Status Only 11…26.4V DC from DeviceNet
Current Available 50 mA max. per input, 200 mA total