182 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Figure 73 - Skip Frequency Band
Stall Fault Time
Sets for the fault time that the drive
will remain in stall mode before a
fault is issued.
0 = 60 sec (Default)
1 = 120 sec
2 = 240 sec
3 = 360 sec
4 = 480 sec
5 = Flt Disabled
Parameter Number 221
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units
Minimum Value 0
Maximum Value 5
Default Value 0
Var PWM Disable
Stop drive before changing this
parameter.
Enables/disables a feature that varies
the carrier frequency for the PWM
output waveform defined by
Parameter 191 (PWM Frequency).
0 = Enabled
1 = Disabled
Disabling this feature when low
frequency condition exists may result
in IGBT stress and nuisance tripping.
Parameter Number 224
Related Parameters 191
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Torque Perf Mode
Stop drive before changing this
parameter.
Enables/disables sensorless vector
control operation.
0 = V/Hz
1 = Sensrls Vect
Parameter Number 225
Related Parameters 184…187, 227
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units
Minimum Value 0
Maximum Value 1
Default Value 1
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band