218 Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 9 Diagnostics
2. Select the Edit Tags tab at the bottom of the screen and create a
tag named Reset of the type BOOL (Boolean).
6. Create a rung in ladder logic for executing the Type 1 Reset.
a. Add an XIC Input and assign it the BOOL tag Reset.
b. Add a Message (MSG) instruction that will be used to execute the
reset. The message instruction can be found in the Input/Output
instruction set tab.
c. The completed rung should look like the one below.
7. Configure the message instruction:
a. Begin by double clicking on the tag name field and entering AS_Reset.
b. Right click on the tag name AS_Reset and select NewAS_Reset.
Vedere la pagina 217