166 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Relay Out Sel
Sets the condition that changes the
state of the output relay contacts.
Parameter Number 155
Related Parameters 133, 156, 192, 240…247,
250…257, 260, 261
Access Rule GET/SET
Data Type UINT
Group Drive Advanced Setup
Units
Minimum Value 0
Maximum Value 22
Default Value 22
Table 21 - Options for the Output Relay Contacts
Options Name Description
0 Ready/Fault (Default)
Relay changes state when power is applied. This indicates the drive is ready for operation. Relay returns drive to shelf state when power is
removed or a fault occurs.
1 At Frequency Drive reached commanded frequency.
2 MotorRunning Motor is receiving power from drive.
3 Reverse Drive is commanded to run in reverse direction.
4 Motor Overld Motor overload condition exists.
5 Ramp Reg Ramp regulator is modifying the programmed accel/decal times to avoid overcurrent or overvoltage fault from occurring.
6 Above Freq Drive exceeds the frequency (Hz) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set threshold.
7 Above Cur Drive exceeds the current (% Amps) value set in Parameter 156 (Relay Out Level) Use Parameter 156 to set threshold.
8 Above DCVolt Drive exceeds the DC bus voltage value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.
9 Retries Exst Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
10 Above Anlg V Option not valid for Bulletin 284E ArmorStart.
11 Logic In 1 An input is programmed as Logic In 1 and is active.
12 Logic In 2 An input is programmed as Logic In 2 and is active.
13 Logic In 1 & 2 Both Logic inputs are programmed and active.
14 Logic In 1 or 2 One or both Logic inputs are programmed and one or both is active.
15 StpLogic Out Drive enters StepLogic step with Digit 3 of Command Word (Parameters 240…247).
16 Timer Out Timer has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.
17 Counter Out Counter has reached value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.
18 Above PF Ang Power factor angle has exceeded the value set in Parameter 156 (Relay Out Level). Use Parameter 156 to set threshold.
19 Anlg In Loss Option not valid for Bulletin 284E ArmorStart.
20 ParamControl Enables the output to be controlled over the network communications by writing to Parameter 156 (Relay Out Level) (0 = OFF, 1 = ON).
21 NonRec Fault Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
22 EM Brk Cntrl EM Brake is energized. Program Parameter 260 (EM Brk OFF Delay) and Parameter 261 (EM Brk On Delay) for desired action.
23 Above Fcmd The Current Command Frequency exceeds the value set in Parameter 156 (Relay Out Level).
24 Msg Control With Drive FRN4.01 or later, this option enables the output to be controlled over the network communication.