130 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Starter Display Group (Bulletin 280E/281E only)
Keypad Mode
This parameter selects if the keypad
operation is maintained or
momentary.
0 = Maintained
1 = Momentary
Parameter Number 45
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Keypad Disable
This parameter disables all keypad
function except for the “OFF” and
“RESET” buttons.
0 = Not Disabled
1 = Disabled
Parameter Number 46
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Set to Defaults
This parameter if set to “1” will set the
device to the factory defaults (but will
not cause the ArmorStart to reboot).
0 = No Operation
1 = Set to Defaults
Parameter Number 47
Access Rule GET/SET
Data Type BOOL
Group Misc. Config.
Units
Minimum Value 0
Maximum Value 1
Default Value 0
Phase A Current
This parameter provides the current of
Phase A measured n increments of
1/10
th
of an ampere.
Parameter Number 101
Access Rule GET/SET
Data Type INT
Group Starter Display
Units xx.x Amps
Minimum Value 0
Maximum Value 32767
Default Value 0