118 Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
InternalLinkStat
Status of the internal network
connections.
Parameter Number 6
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value 31
Default Value 0
Bit
Function:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
——————————————— X Explicit Connection
—————————————— X — I/O Connection
————————————— X —— Explicit Fault
———————————— X ——— I/O Fault
——————————— X ———— I/O Idle
XXXXXXXXXXX————— Reserved
Starter Command
The parameter provides the status of
the starter command.
Parameter Number 7
Access Rule GET
Data Type WORD
Group Basic Status
Units —
Minimum Value 0
Maximum Value 255
Default Value 0
Bit
Function:
76543210
——————— X Run Fwd
—————— X — Run Rev
————— X —— Fault Reset
———— X ——— Reserved
——— X ———— Reserved
—— X ————— Reserved
— X —————— OutA
X ——————— OutB