Function Block Library 4–14
1336 FORCE — 5.9 August 1995
Example 2 — Rate = 16383 Units-per-Second (UPS)
16383
DERIV Out
32767
+16383
Ramp Input Rate = +16383UPS
0
In the example above, the rate limit input to the derivative function is set to allow a
16383UPS change of output. A constant rate-of-change to the input, yields a constant output
level of ±16383, with the output sign changing with the input slope.
DERIV
(continued)
Vedere la pagina 75