1–13Getting Started
1336 FORCE — 5.9 August 1995
2. Enter an offset value of 0 for Parameters 400 and 404. This
allows a value of ±32767 to traverse the entire ±10V range for
both analog outputs.
3. Within the link window at the bottom of the screen, double click
on the Par # field associated with Parameter 387.
Link analog output #1, Parameter 387, to Rate Limiter output
node Output (4:5).
The window shown below should appear with entry boxes.
4. Enter a Task Number of 1.
Enter a Block Number of 4.
Enter a Node Number of 5.
Click on OK.
Link analog output #3, Parameter 389, to Rate Limiter input node
Input 1 (4:0).
Vedere la pagina 24