1–22 Getting Started
1336 FORCE — 5.9 August 1995
— Link Analog Output 1 to the Rate Limit Output
BTW
Data File
N57:0
4 8900 183 8504 0 0 0 0 0 0
0 1 2 3 4 5 6 7 8 9
1. Link Analog Output 1 (Parameter 387) to the Rate Limit output
(Block 4, Node 5).
2. Toggle bit I:00/00 to initiate the block transfer routine which
processes all function block links.
3. Verify that the write was successful. If N57:101 = 0900
hex
(Block
Transfer Read data), there are no errors.
— Link Analog Output 3 to the Rate Limit Input
BTW
Data File
N57:0
4 8900 185 8004 0 0 0 0 0 0
0 1 2 3 4 5 6 7 8 9
1. Link Analog Output 3 (Parameter 389) to the Rate Limit Input
(block 4, node 0).
2. Toggle bit I:00/00 to initiate the block transfer routine which
processes all function block links.
3. Verify that the write was successful. If N57:101 = 0900
hex
(Block
Transfer Read data), there are no errors.