5–40 Block Transfer Services
1336 FORCE — 5.9 August 1995
Example
In this example, a Read Full Node Information message was sent to
the drive. Word 4 shows the present value in drive units. Word 5
through word 8 provide scaling information, used to convert drive
units to engineering units. Word 9 through word 12 provide the
parameter name.
This example shows the response message N10:90 through N10:111
in both binary and ASCII. The parameter name characters return in
reverse order for each word. N10:99 has the ASCII value of aR. To
read this, invert the word to read Ra. The next word, et, inverted
gives you te. These words along with the following two words form
the words Rate Lim.
10
N10:10
23456789
N10:90
BTW
Data File
BTR
Data File
Data Format
8504
8504 CCCE
0000
0000
0F00
0F00 002B 0001 0001 0001 0000 6152
6D69 23206574 4620 2034 754F 2074 8001 7FFF 0000
2020 2020
10
N10:10
23456789
N10:90
BTW
Data File
BTR
Data File
\04
\04 \CC\CE
\00\00
\00\00
\0F\00
\0F\00 \00 + \00\01 \00\01 \00\01 \00\00 a R
m i # e t L 4 u 0 T \01 \7F\FF 0000
ς
à
à
N10:100
N10:110
N10:100
N10:110
Read Full Node
Information
(continued)