Configuring the UDC Module’s Registers
3-33
Drive Fault Register (Continued) 202/1202
Ground Current Fault Bit 2
The Ground Current Fault bit is set if ground
current exceeds the hardware trip point.
Hex Value: 0004H
Sug. Var. Name: FLT_GND@
Access: Read only
UDC Error Code: 1021
LED: EXT FLT
For models A001/Q001 and A003/Q003 the hardware trip point is 20A @ 10V.
For all other models it is 100A @ 10V.
Instantaneous Overcurrent Fault Bit 3
The Instantaneous Overcurrent (IOC) Fault
bit is set if either of the following conditions
is detected:
Hex Value: 0008H
Sug. Var. Name: FLT_IOC@
Access: Read only
UDC Error Code: 1017
LED: P.M. FLT
Output current is greater than 200% of the peak RMS current. Bits 0 to 5 in
register 204/1204 indicate which power device detected the overcurrent.
An inverter power device fault is detected. Bit 6 in register 204/1204 will be set if
the IOC fault is due to a power device overcurrent.
Power Supply Fault Bit 4
The Power Supply Fault bit is set if the
output of the isolated +12V supply, or the
output of the external power supply for a G
or H frame drive, falls below the configured
low voltage threshold.
Hex Value: 0010H
Sug. Var. Name: FLT_12V@
Access: Read only
UDC Error Code: 1022
LED: P.M. FLT
Register 222/1222 provides additional diagnostics if this fault occurs.
Bit 5
Reserved for future use.
Hex Value: 0020H
Sug. Var. Name:
Access: Read only
UDC Error Code: 1023
LED: