DeviceNet Adapter Parameters
B-7
Sets the Logic Command data that is sent to the drive if the
following is true:
Comm Flt Action (10) is set to Send Flt Cfg and communications
are disrupted.
Idle Flt Action (11) is set to Send Flt Cfg and the scanner is put
into Program or Test mode.
Peer Flt Action (34) is set to Fault Cfg and communications are
disrupted.
The bit definitions will depend on the product to which the adapter is
connected.
Sets the Reference data that is sent to the drive if any of the
following is true:
Comm Flt Action (10) is set to Send Flt Cfg and communications
are disrupted.
Idle Flt Action (11) is set to Send Flt Cfg and the scanner is put
into Program mode.
Peer Flt Action (34) is set to Fault Cfg and the scanner is put into
Program mode.
Peer Flt Action (34) is set to Fault Cfg and communications are
disrupted.
Important: If the drive uses a 16-bit Reference, the most significant
word of this value must be set to zero (0) or a fault will
occur.
15 Flt Cfg Logic
Range:
0000 0000 0000 0000 to 1111 1111 1111 1111
Default:
0000 0000 0000 0000
Type:
Read/Write
Reset Required:
No
16 Flt Cfg Ref
Range:
0 to 4294967295
Default:
0
Type:
Read/Write
Reset Required:
No