Instruction Manual
GV3000/SE Operator Interface Module (OIM)
User Guide
Version 2.0
M/N 2RK3000
D2-3342-2
Vedere la pagina 0
1 2 3 4 5 6 ... 111 112

Sommario

Pagina 1 - Version 2.0

Instruction ManualGV3000/SE Operator Interface Module (OIM)User GuideVersion 2.0M/N 2RK3000D2-3342-2

Pagina 2

1-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Although most functions are the same, some functions are performed differently wit

Pagina 3 - Contents

GV3000/SE OIM Menu and Parameter OrganizationB-13•RMI DIG OUT3 DLY TIME (r.042)•RMI DIG OUT4 DLY TIME (r.043)• RMI Relay Outputs•RMI RELAY OUTP 1 CNF

Pagina 4

B-14GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Pagina 5 - List of Figures

Record of User Parameter SettingsC-1APPENDIX CRecord of User Parameter SettingsParameter No. Parameter Name Setting DateP.000 CONTROL SOURCE SELP.001

Pagina 6

C-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0P.029 ELAPSED TIME METERP.030 ELPSD TIME METER RSTP.031 PRESET SPEED 1P.032 PRESET

Pagina 7 - List of Tables

Record of User Parameter SettingsC-3P.068 OUTPUT REG 3 SOURCEP.069 OUTPUT REG 4 SOURCEP.090 DIAGNOSTICS SELECTP.091 DIAGNOSTICS DISPLYP.095 P/M OUTPUT

Pagina 8

C-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0U.004 MOTOR NAMEPL AMPSU.005 MOTOR NAMEPL RPMU.006 MAGNET CURRENT PRCNTU.007 MOTOR

Pagina 9

Record of User Parameter SettingsC-5U.048 OCL PROP TRIM ENABLEr.001 RMI ANLG OUTPUT 1r.002 RMI ANLG OUT 1 OFFSr.003 RMI ANLG OUT 1 GAINr.004 RMI ANLG

Pagina 10 - 1.2 Related Publications

C-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0r.050 RMI SPEED DET LEVEL 1r.051 RMI SPEED DET LEVEL 2r.052 RMI SPEED DET LEVEL 3r

Pagina 11 - Introduction to the OIM

Index Index-1INDEXAACCEL TIME (P.001), 5-11Alarmmenu, 7-5 to 7-6message, 7-1reviewing, 7-5 to 7-6Amperage, motor, 6-1Auto reference, 6-2CChanging para

Pagina 12

Index-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0LLanguage, changing, 3-6LOCAL control source, 6-4Lock symbol, 2-7, 4-4Log, fau

Pagina 13 - Display, and Indicators

Introduction to the OIM1-3For parameter descriptions, fault information, and troubleshooting procedures, see the software I/M that corresponds to your

Pagina 14

IndexIndex-3 SScaled speed units, 1-2Scaling speed units, 3-7 to 3-8Screen contrast, 3-5 to 3-6Second Menu Password (P.006), 4-8Selecting control sour

Pagina 16

U.S. Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: [email protected], Online: www.ab.com/support/abdrives

Pagina 17 - 2.2 The Display

1-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Pagina 18 - 2.2.2 Key Indicators

Description of the OIM Keypad, Display, and Indicators2-1CHAPTER 2Description of the OIM Keypad,Display, and IndicatorsThis chapter describes how to u

Pagina 19

2-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Table 2.1 – Programming Key DescriptionsKey Mode FunctionProgram or MonitorCycles

Pagina 20

Description of the OIM Keypad, Display, and Indicators2-3 Program Move the cursor between menu items or between the parameters and options in the menu

Pagina 21 - Installing, Powering

2-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Program or MonitorWhen the control source is set to OIM, jogs the motor when held

Pagina 22

Description of the OIM Keypad, Display, and Indicators2-52.2 The DisplayOIM screens allow you to program and monitor the drive. Figure 2.2 shows the O

Pagina 23

2-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.02.2.2 Key IndicatorsThe key indicators at the bottom of the display indicate the s

Pagina 24 - 3.2 Powering Up the OIM

Description of the OIM Keypad, Display, and Indicators2-72.2.3 Special Display CharactersThere are several special display characters you might see on

Pagina 25

©1999 Rockwell International CorporationThe information in this manual is subject to change without notice.Throughout this manual, the following notes

Pagina 26

2-8GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Pagina 27

Installing, Powering, and Adjusting the OIM3-1CHAPTER 3Installing, Powering,and Adjusting the OIMThis chapter tells you how to install the OIM, what t

Pagina 28

3-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.03.1.2 Equipment Needed to Install or Replace the OIMTo install or replace the OIM,

Pagina 29

Installing, Powering, and Adjusting the OIM3-3Step 4. Deburr the drilled holes and cutout.Step 5. Remove the backing from the gasket. Place the gasket

Pagina 30

3-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 11. Open the hatch labeled COM PORT ACCESS on the front cover of the GV3000/S

Pagina 31 - Using the OIM

Installing, Powering, and Adjusting the OIM3-5When the power-up sequence is complete, the OIM enters either program mode or monitor mode, depending on

Pagina 32 - Figure 4.1 – Main Menu Screen

3-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 2. Use to increase the contrast (make the screen darker) or to decrease t

Pagina 33

Installing, Powering, and Adjusting the OIM3-73.5 Scaling Speed Units for Your ApplicationYou can scale the speed units to match your application’s re

Pagina 34

3-8GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 3. Move the cursor to Define Speed Units. Press . The Define Speed Units scr

Pagina 35

Installing, Powering, and Adjusting the OIM3-9Step 1. In this screen, you define the units of measure that will be used on the display. The tag can be

Pagina 36

ContentsICONTENTSChapter 1 Introduction to the OIM1.1 Differences Between the OIM and the Front Panel Keypad/Display ... 1-11.2 Related Pu

Pagina 37

3-10GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Using the example of a full scale value of 500.0 and MOTOR TOP SPEED of 1750, the

Pagina 38

Basics of Programming the Drive Using the OIM4-1CHAPTER 4Basics of Programming the DriveUsing the OIMTo program the drive using the OIM, you change th

Pagina 39

4-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0To view the rest of the menu, press . The full Main Menu includes:•Quick Start•Sp

Pagina 40

Basics of Programming the Drive Using the OIM4-3The Main Menu help screen is shown in figure 4.2.In a menu, help gives an overview of the options avai

Pagina 41 - Program the Drive

4-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0•The parameter type is INPUT. This means you can change the value.•The save type i

Pagina 42

Basics of Programming the Drive Using the OIM4-5Step 2. Press . The Speed Control Menu is displayed, as shown in figure 4.6.Step 3. Use to move the

Pagina 43

4-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.04.1.4 Viewing Parameter ValuesIn the parameter lists, parameter values are shown t

Pagina 44 - Regulation

Basics of Programming the Drive Using the OIM4-7.Step 4. If the existing value is shown, go to step 5. If you see a list of options:a. Move the cursor

Pagina 45

4-8GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.04.1.6 Parameter Values that Cannot be ChangedIn some cases, you cannot change para

Pagina 46

Basics of Programming the Drive Using the OIM4-9Step 3. Select the Memory Functions menu.Step 4. Select the PROGRAMMING DISABLE (P.051) parameter. If

Pagina 47

IIGV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Chapter 6 Using the OIM to Monitor and Control the Drive6.1 Using the OIM to Monito

Pagina 48 - REGULATION TYPE (P.048)

4-10GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 4. Select ON. Press . The defaults are restored and you are returned to the

Pagina 49 - MOTOR POLES (U.002)

Using Quick Start to Program the Drive5-1CHAPTER 5Using Quick Start toProgram the DriveThe Quick Start feature on the OIM lets you program the most co

Pagina 50 - MOTOR NAMEPL HP (U.022)

5-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.05.2 Using the Quick Start Exit MenuQuick Start automates the process of entering t

Pagina 51 - ACCEL TIME (P.001)

Using Quick Start to Program the Drive5-35.3 Programming the Drive Using Quick StartImportant:If program protection is enabled, you cannot change Quic

Pagina 52 - MINIMUM SPEED (P.003)

5-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 7. After CURRENT LIMIT (P.005), what happens next depends on the regulation t

Pagina 53 - CURRENT LIMIT (P.005)

Using Quick Start to Program the Drive5-55.4.1 Setting Up the OIM for Self-TuningTo prepare for self-tuning:•Perform the Quick Start procedure (descri

Pagina 54 - MAGNET CURRENT PRCNT (U.006)

5-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 3. Press to clear the screen and continue. The screen shown in figure 5.5 i

Pagina 55 - Control the Drive

Using Quick Start to Program the Drive5-7Step 5. When self-tuning is complete, the OIM displays one of these messages: •Self Tuning has updated the g

Pagina 56

5-8GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.05.5 Quick Start Parameter DescriptionsBrief descriptions of the Quick Start parame

Pagina 57

Using Quick Start to Program the Drive5-9If SENSORLESS is not selected, the value of this parameter is automatically set if torque control self-tuning

Pagina 58

ContentsIIIList of FiguresFigure 2.1 – OIM Keypad, Display, and Indicators ... 2-1Figure 2.2 – OIM Dis

Pagina 59 - 6.3.2 Stopping the Drive

5-10GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0In V/Hz regulation, this parameter configures the V/Hz ratio. Base frequency is t

Pagina 60 - Troubleshooting the Drive

Using Quick Start to Program the Drive5-11The time the motor takes to increase speed is directly proportional to the value in this parameter. This par

Pagina 61

5-12GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0The time the motor takes to decrease speed (except during a coast-to-rest stop) i

Pagina 62 - 7.2.1 Reviewing the Fault Log

Using Quick Start to Program the Drive5-13For V/Hz regulation, this parameter specifies the maximum allowed speed in hertz. The drive is equipped with

Pagina 63

5-14GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0If the motor nameplate shows the no-load current, this parameter value can be cal

Pagina 64 - Figure 7.6 – Alarm Menu

Using the OIM to Monitor and Control the Drive6-1CHAPTER 6Using the OIM to Monitor andControl the DriveThe OIM allows you to monitor the outputs to th

Pagina 65 - Figure 7.8 – Diagnostics Menu

6-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0•Output power: Output power of the drive in kilowatts. This is intended for displa

Pagina 66

Using the OIM to Monitor and Control the Drive6-3Step 4. To go to program mode, press again. As you press , you will cycle between program mode and

Pagina 67 - 7.6 OIM Failures

6-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.06.2 Selecting the Control SourceUse to select the control source for the drive.T

Pagina 68 - Panel Keypad/Display Codes

Using the OIM to Monitor and Control the Drive6-56.3 Using the OIM to Control the DriveWhen the control source is set to OIM, the OIM can be used to c

Pagina 69

IVGV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Pagina 70 - Parameter Numbers

Troubleshooting the Drive Using the OIM7-1CHAPTER 7Troubleshooting the DriveUsing the OIMUsing the OIM, you can troubleshoot drive problems using one

Pagina 71

7-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0The fault screen tells you which fault occurred - in this example, the HIGH LINE V

Pagina 72

Troubleshooting the Drive Using the OIM7-37.2 Reviewing and Resetting Faults Using the Fault MenuThrough the Fault Menu, you can review and reset faul

Pagina 73

7-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 2. To view more information about a particular fault, move the cursor to the

Pagina 74

Troubleshooting the Drive Using the OIM7-5Faults can also be reset without clearing the fault log by:•Pressing when the drive is stopped and the con

Pagina 75

7-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0Step 2. Select Review Active Alarms by pressing . A sample of the screen is shown

Pagina 76 - Input r.010 Option Port

Troubleshooting the Drive Using the OIM7-7Step 2. If the DRIVE READY indicator is off, the drive is not ready to start. If this is the case, move the

Pagina 77

7-8GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.07.6 OIM FailuresThere are three OIM failure states: link failure, fatal OIM errors

Pagina 78 - Input r.015 Option Port

Troubleshooting the Drive Using the OIM7-97.7 Alarm and Fault Names Cross-Referenced to Front Panel Keypad/Display CodesThe following tables list the

Pagina 79

7-10GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0GROUND FAULT FAILURE EC Earth current failure (ground fault)HIGH DC BUS VOLTAGE H

Pagina 80

ContentsVList of TablesTable 2.1 – Programming Key Descriptions ... 2-2Table 2.2 – Control Ke

Pagina 81

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-1APPENDIX AOIM Parameters Cross-Referenced toSoftware I/M Parameters

Pagina 82

A-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0AVOID FREQ ENABLE Avoidance Frequency EnableInput H.009 Application Setup (V/Hz) ⇒

Pagina 83

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-3ENCODER LOSS ENABLEEncoder Loss Enable Input P.039 Application Setu

Pagina 84

A-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0LEVEL SENSE START EN*Level Sense Start EnableInput P.054 Application Setup (V/Hz a

Pagina 85

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-5MOTOR NAMEPL RPM Motor Nameplate RPM Input U.005 Quick Start (Vecto

Pagina 86

A-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0OCL LEAD/LAG RATIO* Outer Control Loop Lead/Lag RatioInput U.043 Performance Tunin

Pagina 87

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-7PRESET SPEED 5 Preset Speed 5 Input P.035 Regulator Terminal Strip

Pagina 88 - Parameter Organization

A-8GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0RMI ANLG OUTPUT 1 Analog Output 1 Source Input r.001 Option PortConfiguration ⇒ RM

Pagina 89

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-9RMI DIG OUT4 DLY TIMEDigital Output 4 Delay TimeInput r.043 Option

Pagina 90

A-10GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0RMI RELAY OUTP 1 CNFRelay Output 1 (NO) ConfigurationInput r.035 Option Port Conf

Pagina 91

VIGV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Pagina 92

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-11RMI TRQ DET LEVEL 2 Torque DetectionLevel 2Input r.064 Option Port

Pagina 93 - • RMI Outputs

A-12GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0*Only supported for GV3000/SE Regulator board versions 6.0 and later.TORQUE REG I

Pagina 94 - B.1.11 Additional Parameters

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-13Table A.2 – OIM Parameters Listed by Parameter NumberParameter Num

Pagina 95

A-14GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0P.037 PRESET SPEED 7P.038 PRESET SPEED 8P.039 ENCODER LOSS ENABLEP.040 MOTOR OVER

Pagina 96

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-15H.006 DC BRAKING START FREQH.007 DC BRAKING CURRENTH.008 DC BRAKIN

Pagina 97

A-16GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0U.023 LOW BUS FLT AVOID ENU.024 HIGH BUS FLT AVOID ENU.025 ZERO SPEED HOLD TIMEU.

Pagina 98

OIM Parameters Cross-Referenced to Software I/M Parameters and Parameter NumbersA-17r.032 RMI DIG OUTPUT 2 CNFr.033 RMI DIG OUTPUT 3 CNFr.034 RMI DIG

Pagina 99

A-18GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

Pagina 100 - B.2.11 Additional Parameters

GV3000/SE OIM Menu and Parameter OrganizationB-1APPENDIX BGV3000/SE OIM Menu andParameter OrganizationThe organization of the OIM menus depends on the

Pagina 101

B-2GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0•DECEL TIME (P.002)•MINIMUM SPEED (P.003)•MAXIMUM SPEED (P.004)•CURRENT LIMIT (P.0

Pagina 102

Introduction to the OIM1-1CHAPTER 1Introduction to the OIMThe Operator Interface Module (OIM) is a keypad and display that connects to Reliance GV3000

Pagina 103

GV3000/SE OIM Menu and Parameter OrganizationB-3•FLD-WEAKEN START RPM (U.016)•MOTOR TOP SPEED (U.017)•AC LINE VOLTAGE (U.018)•CARRIER FREQ (KHZ) (P.04

Pagina 104

B-4GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0• OCL INTEGRAL GAIN (U.046)• OCL TRIM RANGE PERCNT (U.047)• OCL PROP TRIM ENABLE

Pagina 105

GV3000/SE OIM Menu and Parameter OrganizationB-5•TS DIG INP CONFIG (P.007)•TS SPEED REF SEL (P.008)•MOP Configuration• MOP ACCEL DECEL TIME (P.023)• M

Pagina 106

B-6GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0B.1.9 Option Port Configuration Menu (If the Optional RMI Board Is Installed)Optio

Pagina 107

GV3000/SE OIM Menu and Parameter OrganizationB-7•RMI DIG OUT3 DLY TIME (r.042)•RMI DIG OUT4 DLY TIME (r.043)• RMI Relay Outputs•RMI RELAY OUTP 1 CNF (

Pagina 108

B-8GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0B.2 Main Menu - V/Hz Regulation•Quick Start - see B.2.1•Speed Control - see B.2.2•

Pagina 109

GV3000/SE OIM Menu and Parameter OrganizationB-9•Draw & Trim Configure• TRIM REF SOURCE (P.014)• DRAW GAIN PERCENT (P.016)• TRIM GAIN PERCENT (P.0

Pagina 110

B-10GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0• MOTOR OVERLOAD TYPE SEL (P.041)• FLT AUTO RESET COUNTS (P.043)• FLT AUTO RESET

Pagina 111

GV3000/SE OIM Menu and Parameter OrganizationB-11•MOP Configuration• MOP ACCEL DECEL TIME (P.023)• MOP RESET CONFIG (P.024)•Preset Speed Setup• PRESET

Pagina 112

B-12GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0B.2.9 Option Port Configuration Menu (If the Optional RMI Board Is Installed)Thes