DeviceNet Adapter Parameters
B-3
DeviceNet data rate if the data rate switch is set to “PGM”
(Program).
DeviceNet data rate actually used by the adapter.
Size of the Reference/Feedback. The drive determines the size of
the Reference/Feedback.
Size of each Datalink word. The drive determines the size of
Datalinks.
5 DN Rate Cfg
Range:
0 = 125 kbps
1 = 250 kbps
2 = 500 kbps
3 = Autobaud
Default:
3 = Autobaud
Type:
Read/Write
Reset Required:
Yes
6 DN Rate Actual
Range:
0 = 125 kpbs
1 = 250 kbps
2 = 500 kbps
3 = Autobaud
Default:
0 = 125 kbps
Type:
Read Only
Reset Required:
N/A
7 Ref/Fdbk Size
Range:
0 = 16-bit
1 = 32-bit
Default:
0 = 16-bit
Type:
Read Only
Reset Required:
N/A
8 Datalink Size
Range:
0 = 16-bit
1 = 32-bit
Default:
0 = 16-bit
Type:
Read Only
Reset Required:
N/A