Publication 900-UM004D-EN-E - July 2010
Modbus Communications Procedure 4-23
Echoback Test
Figure 4.18 Command Frame
Figure 4.19 Response Frame ➊
➊ When the command is executed normally, the response returns the same data sent in the command.
Test Data
Enter any 2-byte hexadecimal data.
Response Code
Example Command and Response
The following example shows the command/response for an Echoback Test
command.
Table 4.18
Function Code Error Code Name Description
H’88 H’03 Variable data
error
The data following the function
code was not the fixed data
(H’00, H’00).
H’08 — Normal
completion
No errors were found.
Power ON
Software reset command
Setting area 0 Setting area 1
“Move-to-setting
area 1” command
Control in progress Control stopped.
CRC-16
11 2 2
H'08 H'00 H'00
Te st data
2 bytes
Slave
address
Function
code
Write
start address
CRC-16
11 2 2
H'08 H'00 H'00
Te st data
2 bytes
Slave
address
Function
code
Write
start address