Publication 900-UM004D-EN-E - July 2010
3-4 Communications Data
Note: The alarm function can also be used on units without alarm outputs. In this case, confirm alarm occurrences via the status
data.
The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.
C1 (81) 0025 SP ramp set value H’00000000 (0): OFF
H’00000001…H’0000270F (1…9999)
Adjust
ment
C1 (81) 0026 MV upper limit Standard: MV lower limit + 0.1…H’0000041A (MV lower limit +
0.1…105.0)
Heating and cooling: H’00000000…H’0000041A (0.0…105.0)
C1 (81) 0027 MV lower limit Standard: H’FFFFFFCE…MV upper limit 0.1 (5.0…MV upper
limit 0.1)
Heating and cooling: H’FFFFFBE6…H’00000000 (105.0…0.0)
C1 (81) 0028 Move Protect
function group
H’FFFFF831…H’0000270F (1999…9999) Protect
C1 (81) 0029 Password to Move to
Protect function
group
H’FFFFF831…H’0000270F (1999…9999)
(Can only be set. The monitor value is always H’00000000.)
C1 (81) 002A Parameter mask
enable
H’00000000 (0): OFF
H’00000001 (1): ON
C1 (81) 002B PF Key Protect H’00000000 (0): OFF
H’00000001 (1): ON
C1 (81) 002C MV Change Rate
Limit
H’00000000...H’000003E8 (0.0...100.0) Adjust
ment
C1 (81) 002F Heater Overcurrent
Detection 1
H’00000000...H’000001F4(0.0...50.0)
C1 (81) 0030 Heater Overcurrent
Detection 2
H’00000000...H’000001F4 (0.0...50.0)
C1 (81) 0031 Extraction of Square
Root Low-cut Point
H’00000000...H’000003E8 (0.0...100.0)
Table 3.2 Variable Type C1 (81)
Variable
Typ e
Address Item (Parameter) Set (Monitor) Value Function