Publication 900-UM004D-EN-E - July 2010
Modbus Communications Procedure 4-3
Example of Appending the Calculation Result
When the calculated CRC value is H’1234, the CRC value is appended to the
command frame as shown in Figure 4.2.
Figure 4.2
Response Frame
Normal Response Frame
Figure 4.3
Error Response Frame
Figure 4.4
CRC-16
11
Low
H'34
High
H'12
Data
CRC-16 calculation range
2 bytes
Slave
address
Function
code
CRC-16
11
Data
CRC-16 calculation range
2 bytes
Slave
address
Function
code
CRC-16
111
CRC-16 calculation range
2 bytes
Slave
address
Function
code
Error
code