Temperature Controller Communications
Functions
USER MANUAL
Bulletin No. 900-TCx
Vedere la pagina 0
1 2 3 4 5 6 ... 102 103

Sommario

Pagina 1 - Functions

Temperature Controller Communications FunctionsUSER MANUALBulletin No. 900-TCx

Pagina 2 - Important User Information

Publication 900-UM004D-EN-E - July 20101-2 About Communications MethodsCommunications SpecificationsNote: Highlighted characters in the table above in

Pagina 3 - Directive Compliance

Publication 900-UM004D-EN-E - July 20105-18 Communications Data for ModbusNotes:

Pagina 4

A-1 Publication 900-UM004D-EN-E - July 2010Appendix AASCII Tableb4b3b2b1 012345670000 0NULDELSPACE0 @ P \ PEven parity 0001 1SOHDC1! 1 A Q a q0010 2ST

Pagina 5 - Table of Contents

Publication 900-UM004D-EN-E - July 2010A-2Notes:

Pagina 6 - -ii Table of Contents

Publication 900-UM004D-EN-E - July 2011 1-1 © 2011 Rockwell Automation. Printed in the U.S.A.Supersedes Publication 900-TC004C-EN-E - October 2008Bac

Pagina 7 - Conventions Used in This

Publication 900-UM004D-EN-E - July 2010About Communications Methods 1-3InterfaceCommunications with the host device are carried out through a standard

Pagina 8 - How to Read Display Symbols

Publication 900-UM004D-EN-E - July 20101-4 About Communications MethodsRS-232C (Applies to the 900-TC8 only)• RS-232C connections are 1:1.• The total

Pagina 9 - About Communications Methods

Publication 900-UM004D-EN-E - July 2010About Communications Methods 1-5Communications parametersThe 900-TCx's communications specifications are s

Pagina 10 - Transmission procedure

Publication 900-UM004D-EN-E - July 20101-6 About Communications MethodsCommunications Parameter SetupBefore you carry out communications with the 900-

Pagina 11 - Interface

Publication 900-UM004D-EN-E - July 2010About Communications Methods 1-7Communication ParametersNote that communications parameters are enabled after t

Pagina 12

Publication 900-UM004D-EN-E - July 20101-8 About Communications MethodsSetting Communications WritingSet the communications writing parameter to ON to

Pagina 13

2-1 Publication 900-UM004D-EN-E - July 2010Chapter 2Bulletin 900 Communications Procedures900-TCx (CompoWay/F)Data FormatUnless otherwise indicated, n

Pagina 14 - Communications Parameter

Publication 900-UM004D-EN-E - July 20102-2 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Response Frame• The end code is returned for eac

Pagina 15 - Communication Parameters

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-3Communications DataExample of End CodeThe follow

Pagina 16 - Setting Communications

Publication 900-UM004D-EN-E - July 2010-iiImportant User InformationSolid state equipment has operational characteristics differing from those of elec

Pagina 17 - 900-TCx (CompoWay/F)

Publication 900-UM004D-EN-E - July 20102-4 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Example 3: No node number provided Command Forma

Pagina 18 - Response Frame

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-5Structure of Command TextPDU (Protocol Data Unit

Pagina 19 - Example of End Code

Publication 900-UM004D-EN-E - July 20102-6 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Type Code (Variable Type)The following defines v

Pagina 20

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-7Number of ElementsThe number of elements is expr

Pagina 21 - Structure of Command Text

Publication 900-UM004D-EN-E - July 20102-8 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Detailed Description of ServicesRead from Variab

Pagina 22 - Addresses

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-9Response codeNormal CompletionError OccurredTabl

Pagina 23 - List of Services

Publication 900-UM004D-EN-E - July 20102-10 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Write to Variable AreaThis service writes to th

Pagina 24 - Services

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-11Response codeNormal CompletionError OccurredNot

Pagina 25 - Response code

Publication 900-UM004D-EN-E - July 20102-12 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Composite Read from Variable AreaThis service r

Pagina 26 - Write to Variable Area

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-13Error occurredComposite Write to Variable AreaT

Pagina 27

Publication 900-UM004D-EN-E - July 2010-iiiEuropean Communities (EC) Directive ComplianceIf this product has the CE mark it is approved for installati

Pagina 28 - Response Code

Publication 900-UM004D-EN-E - July 20102-14 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Number of Write Data Items (Variable Type + Wri

Pagina 29

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-15Read Controller AttributesThis service reads th

Pagina 30

Publication 900-UM004D-EN-E - July 20102-16 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Read Controller StatusThis service reads the op

Pagina 31 - Read Controller Attributes

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-17Operating statusRelated informationResponse Cod

Pagina 32 - Read Controller Status

Publication 900-UM004D-EN-E - July 20102-18 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Service Response PDUTest dataSet any test data

Pagina 33 - Echoback Test

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-19Operation CommandsThis service performs operati

Pagina 34 - Test data

Publication 900-UM004D-EN-E - July 20102-20 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Command Code and related informationResponse co

Pagina 35 - Operation Commands

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-21Error OccurredDescription of operation commands

Pagina 36

Publication 900-UM004D-EN-E - July 20102-22 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)area 0 and setup area 1. An operation error wil

Pagina 37

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-23– When the mode is switched from RAM write mode

Pagina 38

Publication 900-UM004D-EN-E - July 2010-ivNotes:

Pagina 39

Publication 900-UM004D-EN-E - July 20102-24 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)mode while already in manual mode, the command

Pagina 40

Publication 900-UM004D-EN-E - July 2010Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-251. An operation error will occur if communicati

Pagina 41

Publication 900-UM004D-EN-E - July 20102-26 Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)Response Code ListNormal CompletionError Occurr

Pagina 42 - Response Code List

3-1 Publication 900-UM004D-EN-E - July 2010Chapter 3Communications DataVariable Area (setup range) ListThis chapter lists the details of each of the c

Pagina 43

Publication 900-UM004D-EN-E - July 20103-2 Communications Data➊ Not displayed on the controller’s display➋ When the variable type is 80 (word access),

Pagina 44 - 3-2 Communications Data

Publication 900-UM004D-EN-E - July 2010Communications Data 3-3C1 (81) 0003 Set Point SP lower limit to SP upper limit OperatingC1 (81) 0004 Alarm Valu

Pagina 45 - Communications Data 3-3

Publication 900-UM004D-EN-E - July 20103-4 Communications DataNote: The alarm function can also be used on units without alarm outputs. In this case,

Pagina 46 - 3-4 Communications Data

Publication 900-UM004D-EN-E - July 2010Communications Data 3-5Table 3.3 Variable Type C3 (83)Variable Typ eAddress Item (Parameter) Set (Monitor) Valu

Pagina 47 - Communications Data 3-5

Publication 900-UM004D-EN-E - July 20103-6 Communications DataC3 (83) 0009 ST H’00000000(0): OFF H’00000001(1): ONInitial SettingC3 (83) 000A Control

Pagina 48 - 3-6 Communications Data

Publication 900-UM004D-EN-E - July 2010Communications Data 3-7C3 (83) 0016 Event input assignment 1 ➍H'00000000 (0): NoneH'00000001 (1): RUN

Pagina 49 - Communications Data 3-7

Table of ContentsImportant User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -iiEuropean Communities (EC) Directive

Pagina 50 - 3-8 Communications Data

Publication 900-UM004D-EN-E - July 20103-8 Communications DataC3 (83) 002B Input digital filter H’00000000…0000270F (0.0…999.9) AdvancedSettingFunctio

Pagina 51 - Communications Data 3-9

Publication 900-UM004D-EN-E - July 2010Communications Data 3-9C3 (83) 003E Transfer output type H’00000000 (0): OFFH’00000001 (1): Set pointH’00000002

Pagina 52 - 3-10 Communications Data

Publication 900-UM004D-EN-E - July 20103-10 Communications DataC3 (83) 004E Control output 1 assignmentWhen control output 1 is a linear output: H’00

Pagina 53 - Communications Data 3-11

Publication 900-UM004D-EN-E - July 2010Communications Data 3-11C3 (83) 0054 Soak time unit H’00000000 (0): MinutesH’00000001 (1): HoursAdvanced functi

Pagina 54 - 3-12 Communications Data

Publication 900-UM004D-EN-E - July 20103-12 Communications DataC3 (83) 0071 Monitor/Setting Item 4H’00000000...H’0000000F (0 ...5)* Same as for Monito

Pagina 55 - Status Structure

Publication 900-UM004D-EN-E - July 2010Communications Data 3-13Status StructureFigure 3.1 Structure and Status Data:➊ Applies to the 900-TC8 only0016

Pagina 56 - Bit position

Publication 900-UM004D-EN-E - July 20103-14 Communications DataFigure 3.2 Status Structure Data (Continued)Figure 3.3 Status 2 Structure Data 00031 30

Pagina 57 - Table 3.4 Status Details

Publication 900-UM004D-EN-E - July 2010Communications Data 3-15The table below shows the status details.Table 3.4 Status DetailsBit PositionStatus Bit

Pagina 58 - Table 3.5 Status 2 Contents

Publication 900-UM004D-EN-E - July 20103-16 Communications DataTable 3.5 Status 2 ContentsBit PositionStatus ➊➋ Bit Description01Status (lower word)0

Pagina 59 - Data Format

4-1 Publication 900-UM004D-EN-E - July 2010Chapter 4Modbus Communications ProcedureRead this section if you are to communicate using the Modbus format

Pagina 60 - CRC-16 Calculation Example

Publication 900-UM004D-EN-E - July 2010-ii Table of ContentsRead from Variable Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Pagina 61

Publication 900-UM004D-EN-E - July 20104-2 Modbus Communications ProcedureCRC-16 Calculation ExampleMessages are processed one byte at a time in the w

Pagina 62 - Error Codes

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-3Example of Appending the Calculation ResultWhen the calculated CRC value is

Pagina 63 - Function List

Publication 900-UM004D-EN-E - July 20104-4 Modbus Communications ProcedureError CodesTable 4.2 Slave address The number specified in the command frame

Pagina 64 - Variable Area

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-5No ResponseIn the following cases, the received command will not be processe

Pagina 65

Publication 900-UM004D-EN-E - July 20104-6 Modbus Communications ProcedureVariable AreaThe variable area is the region of memory used to exchange data

Pagina 66 - Detailed Description of the

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-7Modbus Addresses Corresponding to 900-TC (CompoWay/F) Setup Areas 0 and 1Set

Pagina 67

Publication 900-UM004D-EN-E - July 20104-8 Modbus Communications ProcedureExample: D’105.0 → H’0000041A The variables are 4- or 8-digit hexadecimal va

Pagina 68

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-9Table 4.6 Name DescriptionSlave address Specify the 900-TCx’s unit number.Th

Pagina 69 - Write Variable Area

Publication 900-UM004D-EN-E - July 20104-10 Modbus Communications ProcedureFigure 4.8 Response FrameTable 4.7 Name DescriptionSlave address The value

Pagina 70

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-11Reading Undisplayed ParametersIt is possible to read the parameters that ar

Pagina 71

P-1 Publication 900-UM004D-EN-E - July 2010PrefaceSafety PrecautionsSafety Signal WordsThis manual uses the following signal word to mark safety preca

Pagina 72 - Example Command and Response

Publication 900-UM004D-EN-E - July 20104-12 Modbus Communications ProcedureFigure 4.12 Response FrameTable 4.9 Name DescriptionSlave address Specify t

Pagina 73 - Write variable address

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-13Writing Undisplayed ParametersIt is possible to write the parameters that a

Pagina 74

Publication 900-UM004D-EN-E - July 20104-14 Modbus Communications ProcedureExample Command and ResponseThe following example shows the command/respons

Pagina 75 - Response:

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-15Variable Write, Single/Operation CommandThis function performs operations s

Pagina 76

Publication 900-UM004D-EN-E - July 20104-16 Modbus Communications ProcedureCommand Code and Related InformationResponse CodeNormal CompletionTable 4.1

Pagina 77

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-17Error OccurredExample Command and ResponseThe following example shows the c

Pagina 78

Publication 900-UM004D-EN-E - July 20104-18 Modbus Communications ProcedureOperation Commands and Precautions• Communications WritingSet the Communica

Pagina 79

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-19– When the mode is switched from RAM write mode to backup mode, the paramet

Pagina 80

Publication 900-UM004D-EN-E - July 20104-20 Modbus Communications Procedure· Moving the Protect function group in Manual ModeWhen this operation comma

Pagina 81

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-21· Switching to Manual Mode during Auto-TuningIf the mode is switched during

Pagina 82

Publication 900-UM004D-EN-E - July 2010P-2 PrefaceHow to Read Display SymbolsThe following table shows the relationship between the symbols exhibited

Pagina 83 - Range) List

Publication 900-UM004D-EN-E - July 20104-22 Modbus Communications Procedure• Alarm Latch CancelThe applicable alarm latch can be cleared with the rela

Pagina 84 - Setting

Publication 900-UM004D-EN-E - July 2010Modbus Communications Procedure 4-23Echoback TestFigure 4.18 Command FrameFigure 4.19 Response Frame ➊➊ When th

Pagina 85

Publication 900-UM004D-EN-E - July 20104-24 Modbus Communications Procedure(In this case, the test data is H’1234 and the slave address is H’01.)Figur

Pagina 86

5-1 Publication 900-UM004D-EN-E - July 2010Chapter 5Communications Data for ModbusThis section lists the details of the communications data in the Mod

Pagina 87

Publication 900-UM004D-EN-E - July 20105-2 Communications Data for Modbus➊ Not displayed on the controller display.➋ In 2-byte mode, the rightmost 16

Pagina 88

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-3Table 5.2 Address Parameter Name Setting (Monitor) Value Function GroupFour B

Pagina 89 - Four-byte mode Two-byte mode

Publication 900-UM004D-EN-E - July 20105-4 Communications Data for Modbus➊ The alarm function can also be used in Controllers without alarm output ter

Pagina 90

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-5Table 5.4 ➊The alarm function can also be used in Controllers without alarm o

Pagina 91

Publication 900-UM004D-EN-E - July 20105-6 Communications Data for Modbus➊ The input type can be selected to match the connected sensor. There are two

Pagina 92

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-7Table 5.6 Address Parameter Name Setting (Monitor) Value Function GroupFour-b

Pagina 93

1-1 Publication 900-UM004D-EN-E - July 2010Chapter 1About Communications MethodsIntroductionThis chapter briefly describes the supported communication

Pagina 94

Publication 900-UM004D-EN-E - July 20105-8 Communications Data for Modbus➊ The program end output can be set when the Program Pattern is not set to 0

Pagina 95

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-9➊ The setting (monitor) range depends on the Transfer Output Type setting. (S

Pagina 96 - Figure 5.1 Status Structure

Publication 900-UM004D-EN-E - July 20105-10 Communications Data for Modbus➊ The parameter will not be shown on the Controller display when Alarm 3 is

Pagina 97 - Figure 5.3 Status 2 Structure

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-11Table 5.10 Address Parameter Name Setting (Monitor) Value Function GroupFour

Pagina 98 - Table 5.11 Status Details

Publication 900-UM004D-EN-E - July 20105-12 Communications Data for Modbus1200 3200 PF Setting H'00000000 (0): NoneH'00000001 (1): RunH&apos

Pagina 99 - Table 5.12 Status 2 Details

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-13➋ The logic of the Modbus variable writing function (Operation command) is n

Pagina 100

Publication 900-UM004D-EN-E - July 20105-14 Communications Data for ModbusStatusFigures 5.1, 5.3 and 5.3 and Tables 5.11 and 5.12 show the structure o

Pagina 101

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-15Figure 5.3 Status 2 Structure0615141312111010000Bit position Spare OutputsSp

Pagina 102

Publication 900-UM004D-EN-E - July 20105-16 Communications Data for Modbus➊When the control output ON time is less than 190 ms, the bit is set to “1”

Pagina 103 - Back Cover

Publication 900-UM004D-EN-E - July 2010Communications Data for Modbus 5-17Table 5.12 Status 2 DetailsBit Position Status Bit Description01Status (low