B-4 Adapter Parameters
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
25 [Flt Cfg Logic]
Sets the Logic Command data that is sent to the
drive if any of the following is true:
• Parameter 21 - [Comm Flt Action] is set to ‘4’
(Send Flt Cfg) and I/O communication is
disrupted.
• Parameter 22 - [Idle Flt Action] is set to ‘4’
(Send Flt Cfg) and the controller is idle.
• Parameter 41 - [Peer Flt Action] is set to ‘4’
(Send Flt Cfg) and peer I/O communication is
disrupted.
The bit definitions depend on the product to which
the adapter is connected. See Appendix D or the
documentation for the drive being used.
Default: 0000 0000 0000 0000
Minimum: 0000 0000 0000 0000
Maximum: 1111 1111 1111 1111
Type: Read/Write
Reset Required: No
26 [Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
any of the following is true:
• Parameter 21 - [Comm Flt Action] is set to ‘4’
(Send Flt Cfg) and I/O communication is
disrupted.
• Parameter 22 - [Idle Flt Action] is set to ‘4’
(Send Flt Cfg) and the controller is idle.
• Parameter 41- [Peer Flt Action] is set to ‘4’
(Send Flt Cfg) and peer I/O communication is
disrupted.
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses a 16-bit
Reference, the most significant word of
this value must be set to zero (0) or a
fault will occur.
27
28
29
30
31
32
33
34
[Flt Cfg A1 In]
[Flt Cfg A2 In]
[Flt Cfg B1 In]
[Flt Cfg B2 In]
[Flt Cfg C1 In]
[Flt Cfg C2 In]
[Flt Cfg D1 In]
[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the
drive if any of the following is true:
• Parameter 21 - [Comm Flt Action] is set to ‘4’
(Send Flt Cfg) and I/O communication is
disrupted.
• Parameter 22 - [Idle Flt Action] is set to ‘4’
(Send Flt Cfg) and the controller is idle.
• Parameter 41 - [Peer Flt Action] is set to ‘4’
(Send Flt Cfg) and peer I/O communication is
disrupted.
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses 16-bit
Datalinks, the most significant word of
this value must be set to zero (0) or a
fault will occur.
35 [M-S Input]
Sets the Master-Slave input data. This data is
produced by the scanner and consumed by the
adapter.
Default: xxx0 0001
Bit Values: 0 = I/O disabled
1 = I/O enabled
Type: Read/Write
Reset Required: Yes
Parameter
No. Name and Description Details
Bit
Definition
Not Used
Not Used
Not Used
Datalink D Input
Datalink C Input
Datalink B Input
Datalink A Input
Cmd/Ref
Default x x x 0 0 0 0 1
Bit 76543210