Rockwell-automation 20-COMM-E PowerFlex EtherNet/IP Adapter Manuale Utente Pagina 196

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 296
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 195
6-70 Using Explicit Messaging
20-COMM-E EtherNet/IP Adapter User Manual
Publication 20COMM-UM010G-EN-P
In this example, the parameters have the following values.
Figure 6.89 Example Scattered Read Response Data File for PowerFlex 750-Series
Drive
The PowerFlex 750-Series drive uses 32-bit integer and REAL parameters.
A COP or CPW command must be used to copy the N60 integer array to a
16-bit integer or floating tag. Figure 6.90
shows the ladder logic used for
this example. If the parameter data type is a 32-bit integer, the data remains
split into two 16-bit integers because there are no 32-bit integers in the
MicroLogix 1100/1400 controller. If the parameter data type is a REAL,
then the destination tag is a floating point. See the drive documentation to
determine the parameter data type (32-bit integer or REAL).
Figure 6.90 Example Ladder Logic to Copy Response Data for PowerFlex 750-Series
Drive
PowerFlex 7-Class Drive Parameter Address Read Value
1 - [Output Freq] N60:1 32.5 Hz
3 - [Output Current] N60:4 0.01 Amp
6 - [Output Voltage] N60:7 118.7V AC
12 - [DC Bus Voltage] N60:10 329.2V DC
17 - [Analog In2 Value] N60:13 8.318 mA
Parameter 137 -
[Open Loop Fdbk]
PowerFlex
750-Series Drives
Parameter 001 -
[Output Freq]
Vedere la pagina 195
1 2 ... 191 192 193 194 195 196 197 198 199 200 201 ... 295 296

Commenti su questo manuale

Nessun commento