Triguard
EXTERNAL
CONNECTIONS
All
connections
to
the
MHB44IND
are
made
via
DIN
41612
connectors.
The
upper
connector
is
the
system
triple
I/O
bus
connector.
The
middle
connector
is
for
the
field
inputs
and
outputs.
The
lower
connector
is
electrically
in
parallel
with
the
middle
connector.
System
interface
This
MHB44IND
acts
as
a slave
to
the
MPP
masters,
and
communication
between
three
MPPs
and
the
MHB44IND
takes
place
over
the
triplicated
16
bit
parallel
I/O
-
MPP
buses
that
run
along
the
chassis
mounted
backplane.
The
three
I/O
-
MPP
buses
are
connected
via
the
module’s
upper
syst
em
interface
DIN
41612
connector.
Field
interface
The
MHB44IND
input,
output
and
feedback
connections
are
wired
via
one
of
the
connectors
(J2
or
J3)
to
the
termination
card
TPH44AIC.
Pulse
inputs
Four
isolated
voltage
inputs
of
100mV
to
150V
peak
to
peak
are provided.
Each
pulse
input
channel
has
both
its
lines
connected
via
100k
ohm
resistors
to
the
test
jacks
and
a front
panel
mounted
LED
flashes
to
indicate
when
pulses
are
being
received.
Current
loop
outputs
Four
0 to
22mA
with
common
return.
The
termination
card
has
a precision
resistor
for
each
channel
to
control
the
current.
This
allows
two
modules
to
be
used
for
dual
-
slot
hot
repair
purposes
using
the
same
termination
card.
CONFIGURATION LINKS
The
module
contains
a hardware
identity
circuit
that
enables
system
identification
of
the
module,
and
seven
manual
configuration
links,
JP1
to
JP4
and
LK1,
LK2
and
LK3.
Links
JP1
to
JP4
and
LK1
to
LK3
Links
JP1
to
JP4
enable
undercurrent
and
overcurrent
monitoring
from
a special
termination
card
giving
ga
lvanically
isolated
outputs.
Links
JP1
to
JP4
must
beset
to
the
Off
position.
Links
LK1
to
LK3
are
described
in
Section
2.6,
Theory
of
operation.
POWER SUPPLIES
The
MHB44IND
operates
from
dual
power
inputs
supplied
by
the
system’s
dual
redundant
PSUs,
that
each
supply
voltages
of
approximately
5.4Vdc
and
12Vdc.