Triguard
SC300E MHB44IND Pulse Input and Analogue Output Module
Pulse Inputs
The
overall
period
of
one
or
more
cycles
of
the
input
is
measured.
Frequency
is
calculated
by
dividing
the
number
of
cycles
by
the
overall
period.
The
pulse
input
voltage
on
each
independent
path
passe
s via
an
isolating
transformer
to
an
amplifier,
which
compensates
for
the
frequency
characteristics
of
the
transformer
and
performs
automatic
level
control
to
cater
for
the
wide
range
of
input
amplitude
(see
Figure
2
-
2).
The
amplifier
output
is
converted
t
o a
pulse
train
feeding
a 16
-
bit
frequency
counter
controlled
by
the
Common
Interface
(CI).
Voting
of
the
frequency
data
between
paths
is
performed
by
the
RTTS.
The
pulse
trains
from
all
three
independent
paths
are
combined
and
trigger
circuits
which
caus
e the
front
-
panel
LEDs
to
flash.
The
four
red
LEDs,
corresponding
to
the
pulse
-
input
channels,
flash
when
pulse
trains
are
being
received.
Four
pairs
of
sockets
are
provided
for
monitoring
the
input
lines
via
100k
ohm
resistors.
Figure
2
-
2 Pulse
input
section
-
Schematic
block
diagram
Commenti su questo manuale