12
MHB44IND
October
200
5
I
ssue 2
Triguard
SC300E
Analogue outputs
Five
test
-
sockets
are
provided
for
monitoring
the
output
lines:
one
common
terminal
via
2.2k
ohm
to
the
+24V
field
supply,
and
the
other
four
via
10k
ohm
to
the
current
-
determining
resistors
on
the
termination
card.
These
resistors
are
250
ohm,
so
20mA
of
loop
-
current
corresponds
to
5V
across
them.
The
four
analogue
voltage
outputs
use
12
-
bit
DACs
to
produce
+0.4V
to
6V
with
respect
to
field
+24V
common,
applied
across
resistors
on
the
termination
car
d.
The
outputs
from
the
three
channels
go
through
a voting
scheme
using
FETs
to
select
the
middle
-
value
output,
so
that
if
one
channel
fails
high
or
low,
one
of
the
other
two
outputs
will
be
selected
(see
Figure
2
-
3).
The
resultant
current
of
0 to
22mA
determined
by
the
voltage
and
resistor
is
fed
to
the
field
device,
then
returns
to
the
supply
negative
via
the
termination
card.
Figure
2
-
3 Analogue
output
section
-
Schematic
block
diagram
Vedere la pagina 11