Rockwell-automation Logix5000 Controllers Sequential Function Charts P Manuale Utente Pagina 80

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 88
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 79
Chapter 3 Force steps
Important: The ForceStatus attribute shows only the status of I/O forces. It does not show the status of SFC
forces.
where:
Force_Status is a DINT tag.
To determine if Examine this bit For this value
forces are installed 0 1
no forces are installed 0 0
forces are enabled 1 1
forces are disabled 1 0
To override a false transition one time and go from an active step to the next step,
use the Step Through option.
You do not have to add, enable, disable, or remove forces.
The next time the SFC reaches the transition, it executes according to the
conditions of the transition.
This option also lets you override one time the false force of a simultaneous path.
When you step through the force, the SFC executes the steps of the path. Follow
these steps to step through the transition of an active step or a force of a
simultaneous path.
1. Open the SFC routine.
2. Right-click the transition or the path that is forced and then click Step
Through.
Step through a transition or
a force of a path
80 Rockwell Automation Publication 1756-PM006F-EN-P - October 2014
Vedere la pagina 79
1 2 ... 75 76 77 78 79 80 81 82 83 84 85 86 87 88

Commenti su questo manuale

Nessun commento