Rockwell-automation Logix5000 Controllers Sequential Function Charts P Manuale Utente Pagina 79

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 88
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 78
Force steps Chapter 3
Forces tab ---------->
Forces tab status Means
Enabled
If the project contains any forces of this type, they are overriding your logic.
If you add a force of this type, the new force immediately takes effect
Disabled
Forces of this type are inactive. If the project contains any forces of this type,
they are
not overriding your logic.
Installed At least one force of this type exists in the project.
None Installed No forces of this type exist in the project.
Force LED
If your controller has a FORCE LED, use the LED to determine the status of any
I/O forces.
Important: The FORCE LED shows only the status of I/O forces. It does not show that status of SFC forces.
If the FORCE LED is Then
Off
No tags contain force values.
I/O forces are inactive (disabled).
Flashing
At least one tag contains a force value.
I/O forces are inactive (disabled).
Solid
I/O forces are active (enabled).
Force values may or may not exist.
GSV instruction
This example shows how to use a GSV instruction to get the status of forces.
Rock well Automati on Publication 1756-PM006F-EN-P - Oct ober 2014 79
Vedere la pagina 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 87 88

Commenti su questo manuale

Nessun commento