ArmorStart Local Control Configuration Chapter 4
17. Click the down arrow.
18. Click the ‘+’ next to Hardware Boolean.
19. Double-click Run Fwd.
20. Connect the BAND block
to the Run Fwd tag.
21. From the Edit pull-down menu, choose
Recovery Mode.
22. Click Enabled.
23. Click OK.
24. Click the Logic Verify icon on the
toolbar to determine if the program is
valid and error-free.
If the logic is valid and passed
certification, the following dialog box
appears.
25. Click OK.