8. Double-click the ArmorStart device on a specific node address.
a. Upload the devices properties if they have not been yet.
b. Click Parameters on the device properties tab.
c. For the ArmorStart 280D and 281D device, make sure the consumed IO Assy is 160 and the Produce
IO Assy is 161.
d. Change any other parameter as needed for your specific application.
e. For the ArmorStart 284D device, make
sure the Consumed IO Assy is 164 and
the Produced IO Assy is 165.
Change any other parameter as needed for
your specific application.