Publication IASIMP-QS015C-EN-P - August 2011 73
ArmorStart DeviceNet Configuration Chapter 3
4. Make sure the controller tags are in ‘Monitor Tags’ mode and not ‘Edit Tags’ mode by checking the tab
field at the bottom.
5. Expand the Local:1:0 (output tags) and within it, expand the Local:1:0.CommandRegister tag as shown.
6. Locate the Local:1:0.CommandRegister.Run value and if set to 0, change value to 1.
7. Check the DeviceNet scanner module on the controller and it should read ‘Run’ on it.
Test Procedure
1. Place the keyswitch in the Run position.
2. Double-click Controller Tags.