ArmorStart EtherNet/IP Distributed Motor Controller Getting Started 13
ArmorStart Receptacle Pin
Outs
Figure 13 – Receptacle Connections for EtherNet/IP (M12)
Figure 14 – Receptacle Connections for Input (M12)
Figure 15 – Receptacle Connections for Output, EtherNet/IP Version (M12)
Figure 16 – Receptacle Connections for Dynamic Brake (M22) – Bulletin 284E only
Pin 1: Tx+
Pin 2: Rx+
Pin 3: Tx–
Pin 4: Rx–
Pin 1: +24V (A3 or DNET)
Pin 2: Input 0
Pin 3: Common
Pin 4: Input 1
Pin 5: NC (no connection)
Pin 1: NC (no connection)
Pin 2: NC (no connection)
Pin 3: Common
Pin 4: Output +24V DC (A1)
Pin 5: NC (no connection)
Pin 1: GND (green/yellow)
Pin 2: BR+ (black)
Pin 3: BR- (white)