10 ArmorStart EtherNet/IP Distributed Motor Controller Getting Started
Publication 280E-QS001B-EN-P – February 2011
Factory installed ArmorConnect gland plate connections
Figure 11 – ArmorConnect Connections
Control Power Wiring
ArmorStart EtherNet/IP utilizes 24V DC control power for communications
and I/O. The control power terminal connections are labeled A1,A2, and A3.
Switched power will supply the outputs. Unswitched power will supply logic
power and sensor inputs. The diagram below provides the user an example of the
internal and external connections for proper operation.
Table 2 - ArmorConnect Gland Plate Conductor Color Code
Terminal Designations Description Color Code
A1 (+) Control Power Input Blue
A2 (–) Control Power Common Black
A3 (+) Unswitched Control Power Red
PE Ground Green/Yellow
1/L1 Line Power – Phase A Black
2/L2 Line Power – Phase B White
3/L3 Line Power – Phase C Red