72 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 5 Programmable Parameters
Reset/Lock Group
L1 Loss Trip Delay
This parameter allows the installer to
program a time duration for which a loss on
line 1 must exist prior to the device tripping.
Parameter Number 128
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-115
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.5
Maximum Value 25.0
Default Value 0.5
L2 Loss Trip Delay
This parameter allows the installer to
program a time duration for which a loss on
line 2 must exist prior to the device tripping.
Parameter Number 129
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-116
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.5
Maximum Value 25.0
Default Value 0.5
L3 Loss Trip Delay
This parameter allows the installer to
program a time duration for which a loss on
line 3 must exist prior to the device tripping.
Parameter Number 130
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-117
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.5
Maximum Value 25.0
Default Value 0.5
TRIP RESET
This parameter provides the user with the
capability of resetting a trip over the
DeviceNet network. After a trip is reset, the
parameter automatically returns to a
“Ready” state.
Parameter Number 26
Access Rule Get/Set
Data Type BOOL
Object Mapping 0x29-1-126
Group Reset/Lock
Units —
Minimum Value 0 = Ready
Maximum Value 1 = Reset
Default Value 0