Rockwell-automation 193-EC4 EC4 Current Monitoring Relay User Manual Manuale Utente Pagina 101

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 100
102 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 9 Logic Controller Application Example with Explicit Messaging
Destination: Integer_Files[1]
Next, set up the communications path in the Communication tab to read data
from the EC4 Current Monitoring Relay located at Node 6 by configuring the
communication Path as “DNET, 2, 6”
DNET - the name of the 1769-SDN DeviceNet Scanner
2 – The port number of the 1769-SDN DeviceNet Scanner
6 – The node address of the EC4 Current Monitoring Relay
When finished, the MSG instruction will read the Device Status from the EC4
Current Monitoring Relay and place the results in Integer_Files[1] as shown:
Vedere la pagina 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 156 157

Commenti su questo manuale

Nessun commento