Rockwell-automation 1785-ENET USER MANUAL PLC-5 ETHERNET INTERFACE Manuale Utente Pagina 13

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 54
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 12
1785-6.5.19 November 1998
Quick Start 1-5
A. Be sure channel 3A is designated as the channel supporting the
1785-ENET module.
Your programming software must support configuration for
channel 3A.
The PLC-5 processor must contain the proper firmware
revision. See chapter 2.
If you are configuring online and the interface module is
attached to the processor, channel 3A will automatically
support the interface module.
If you are configuring offline, follow the steps listed in your
programming software documentation.
B. Specify Ethernet-specific configuration information (including
the IP address) using any one of these methods:
manually configure channel 3A using your programming
software
use a BOOTP server already on your network (see your
Ethernet network administrator for assistance).
Rockwell Automation offers a BOOTP tool on
http://www.ab.com
Important: Assign a diagnostics file to store all status information for
channel 3A. Use your programming software to select an unused
integer file number (10-999). The software creates an integer file that
is 44 words long.
Step 7 Configure channel 3A for Ethernet communication. See Chapter 3
Configuring the Interface
Module for Ethernet
Communication