Specifications A–2
Publication 1771-UM002A–EN–P – May 2000
Agency Certification
(when product is marked)
CSA certified
CSA Class 1, Division 2, Groups A, B, C and D certified
UL listed
CE marked for all applicable directives
C-Tick marked for all applicable acts
1 You use this conductor category information for planning conductor routing as described in publication 1770-4.1,
Industrial Automation wiring and Grounding Guidelines.
Stepper Controller Module Specifications (cat. no. 1771-M1)
Module Location Bulletin 1771 I/O Rack
1 module slot
Backplane Power Requirement 1.75A, 5V dc maximum
Maximum Number of Axes Up to 3 Pulse Output Expander Modules (cat. no.
1771-OJ) for control of up to 3 axes
Keying Insert keying bands between:
2 and 4, and
8 and 10
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
0
o
to 60
o
C (32
o
to 140
o
F)
-40
o
to 85
o
C (-40
o
to 185
o
F)
5 to 95% (without condensation)