Rockwell-automation 1771-DB Basic Module User Manual - Series A Manuale Utente Pagina 36

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 167
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 35
Using the Serial Ports
Chapter 4
4–12
Figure
4.9
Point-to-Point RS-422 Connections
Figure 4.10
Multi-drop configuration with master and multiple slaves
Important: When you use the peripheral port as a 422 port, you must
connect pin 4 to pin 5 on the port.
When using an RS-422 interface you must install termination resistors at
each end of the line. The module has a jumper selectable termination
resistor (Refer to figure 3.2). Use a cable with 2 twisted pairs and a
nominal impedance of 100 ohms.
Important: Use terminating resistors only at the ends of the link if using
multiple RS-422 devices, and at both ends if using point-to-point
connections.
4.4.5
Connecting
RS-422 Devices
(continued)
Vedere la pagina 35
1 2 ... 31 32 33 34 35 36 37 38 39 40 41 ... 166 167

Commenti su questo manuale

Nessun commento