Publication GMC-RM001A-EN-P July 2001
A-4 Noise Control Supplement
Figure A.3
Gland clamping method
Conductive gland grounding, as shown in Figure A.3, is only required
for extreme applications, such as radar, aerospace, etc. The table
below lists advantages and disadvantages of the gland clamp method.
Advantages of gland clamp method: Disadvantages of gland clamp method:
Most effective method
Cost (very expensive)
Each size will accommodate a limited range
of diameters
Excellent strain relief
Only appropriate when passing through a
bulkhead