Rockwell-automation AutoMax Enhanced Ladder Language Reference Manual Manuale Utente Pagina 149

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 352
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 148
7Ć3
7.1.1 Input
P
arameters for the Convert Integer Data to BCD Instruction
This table lists the inputs for the TO_BCD instruction and the variable and type and data
type/range that each input supports.
Parameter
Description V
ariable T
ype Data Type/Range
EN While this input is true, the instruction executes. When this
input is false, the instruction is not executed and ENO is
false.
Connect a Boolean input or output.
In Enter the variable that you want converted to binary
coded data.
D simple
D constant
D element of an array
D integer
(0 to 9999)
D double integer
(0 to 99999999)
D timer
(name.TPreset
and
name.Elapsed)
D counter
(name.CPreset
and
name.Current)
Vedere la pagina 148
1 2 ... 144 145 146 147 148 149 150 151 152 153 154 ... 351 352

Commenti su questo manuale

Nessun commento