88 Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Chapter 5 Preventative Maintenance and Component Replacement
3. Remove the nylon nuts which connect the Voltage Sensing Board to the
Insulation Board.
Figure 28 - Remove the Voltage Sensing Board from the Insulation Board
4. Install the new Voltage Sensing Board to the Insulation Board in reverse
order of removal.
5. Reinstall the Insulation Board to the cabinet side sheet in reverse order of
removal.
6. Reconnect the input and output cables according to the Electrical
Drawings.
Inspect Door Position Limit Switch
Check for obvious signs of damage, dust, or foreign material. Remove any dirt or
foreign material. Wipe components with an anti-static cloth, where applicable.
Check the aviation plug has a hand-tight connection.
Nylon M10 Nut (x9)
Nylon M10 Nut (x9)
Insulation Board
Voltage Sensing Board