58 Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
Chapter 4 Parameters and Function Codes
P090 Skip Frequency 1 Lower Limit 0 ON 0 75
P091 Skip Frequency 1 Upper Limit 0 ON 0 75
P092 Skip Frequency 2 Lower Limit 0 ON 0 75
P093 Skip Frequency 2 Upper Limit 0 ON 0 75
P113 Flying Start-Initial Output Voltage Percentage (%) 5 ON 0 100
P114 Flying Start-Current Comparison Delay For Motor Speed
Search (ms)
1000 ON 0 5000
P115 Flying Start-Current Threshold For Successful Motor
Speed Search
5ON0100
P198 HECS Rated Current (A) 0 ON 0 5000
P199 Motor Rated Current (A) 0 ON 0 5000
P200 Ia Motor Current Memory Address 13 ON 0 500
P201 Motor Ia Scaling Correction Factor 100 ON 0 199.99
P202 Ib Motor Current Memory Address 14 ON 0 500
P203 Motor Ib Scaling Correction Factor 100 ON 0 199.99
P204 Motor Uab Voltage Address 11 ON 0 500
P205 Motor Uab Voltage Scaling Factor Correction 199.99 ON 0 199.99
P206 Motor Uac Voltage Scaling Factor Correction 199.99 ON 0 199.99
P211 Filter Time For Abnormal Output Voltage (ms) 1000 ON 0 32767
P212 Filter Time For Output Short-Circuit (ms) 10 ON 0 32767
P213 Output Short-Circuit Fault Threshold 180 ON 0 199.99
P214 Over Current Low/High Speed Region Boundary 5 ON 0 100
P215 Filter Time For Output Over Current (0.1 s) 200 ON 0 32767
P216 High-Frequency Output Over Current Threshold 120 ON 0 199.99
P217 Low-Frequency Output Over Current Threshold 70 ON 0 199.99
P218 Filter Time For Motor Over Temperature (0.1 s) 6000 ON 0 32767
P219 Motor Over Temperature Warning Threshold 110 ON 0 199.99
P220 Motor Over Temperature Fault Threshold 120 ON 0 199.99
P221 Filter Time For Output Over Voltage (ms) 100 ON 0 32767
P222 Output Over Voltage Fault Threshold 130 ON 0 199.99
P223 Output Voltage Deviation Warning Threshold 60 ON 0 199.99
P224 Output Voltage Deviation Fault Threshold 80 ON 0 199.99
P225 Motor Over Temperature Warning Cancellation
Temperature
100 ON 0 199.99
P226 Output Voltage Abnormality Warning Cancellation
Threshold
50 ON 0 199.99
P227 Ground Fault Detection Scaling Correction Factor 100 ON 0 199.99
P228 Filter Time For Ground Fault (ms) 1000 ON 0 32767
P229 Ground Fault Warning Threshold 20 ON 0 199.99
P230 Ground Fault Trip Threshold 60 ON 0 199.99
P231 Filter Time For Overspeed Fault (Upper Limit) 100 ON 0 32767
Parameter
Number
Description Default
Value
Modify
Root
Lower
Limit
Upper
Limit