76 Rockwell Automation Publication 6000-IN007A-EN-P - October 2014
Chapter 4 No-load Test
Operate Motor by HMI
1. From the Main Interface Screen, press the Set Frequency: input field.
2. In the Set Freq: dialog box, enter a value of “5” and press .
Press to confirm.
IMPORTANT
Before completing this procedure, verify there are no warnings or failure
messages on the HMI. The “Ready” status indicator must be red.
TIP
The Set Frequency and Actual Frequency occasionally will not show the exact
integral value selected, due to internal data conversion in the HMI program.